ADR 0026: 1W enrollment is required, and its safety comes from a physical interlock

Status: Accepted · Recorded: 2026-08

Context

A 1W device only acts on commands from source addresses it has itself registered as a controller, via its own association-mode procedure — not merely from anyone holding the right key. That makes enrollment (registering the hub as a controller) the precondition for any 1W command this project sends ever moving anything, including devices the hub already drives over 2W. Since the hub can register itself as a controller on hardware it does not own, the question this ADR settles is: what makes that safe to ship with no confirmation step in front of it?

Options considered

  1. An arming switch, following ADR 0021's bootloader-rewrite precedent: a hub-level entity that must be turned on before the enroll button will transmit, visible in Home Assistant so "am I about to do this" is answerable by looking.
  2. A software confirmation window (press once to arm, press again within N seconds to commit).
  3. No software gate at all — rely on constraints the protocol and this feature's own design already provide.

Decision

Option 3. There is no arming switch and no confirmation window. Two independent properties make this safe, not one:

1. Only a person standing at the receiver can ever open the window a 0x30 needs. Enrollment is two-sided, and only one side is something the hub can ever emit:

Half Who does it What it is
Receiver enters association mode a person, physically a physical gesture on the receiver side, confirmed by the actuator's own indicator: a multi-second hold on the actuator's own PROG button (Somfy), or a ~1 second GEAR press on an already-registered control (VELUX)
Controller offers its credential the hub one short 0x39 burst, immediately followed by one short 0x30 burst — the documented pairing handshake, see "What the enroll button sends" below

A device that is not in association mode does not accept a 0x30 at all. So a hub sitting on someone's shelf, or one whose YAML happens to carry enrollment: true for longer than intended, cannot enroll into anything: no device is listening. This interlock cannot be triggered from software or from range — someone has to be standing at the actuator with their finger on it.

2. Even a successful enrollment only adds a controller; it does not remove another one. A device that already has a registered remote keeps obeying that remote after the hub also enrolls — enrollment is additive across controllers, not a takeover. This bounds the consequence of the first property ever failing (an enrollment nobody meant to trigger still leaves every existing controller working), independently of whatever bounds who can trigger it in the first place. Neither property depends on the other: the interlock would still be worth having even if enrollment were destructive, and additive registration would still limit the blast radius even if the interlock were somehow bypassed.

Both properties fall out of how the protocol and this feature are already built — neither had to be added for safety's sake.

ADR 0021's arming switch exists for a different risk shape: an irreversible bootloader write, where one more entity is a fair price for the write's own sake. Borrowing that pattern here would add friction without adding safety, since the thing that actually makes a stray enrollment attempt harmless — nobody performing that physical gesture on the receiver, and nothing being displaced even if someone is — is already present with or without a switch.

What the build flag (enrollment: true) is for instead: not safety against a stray press, but against the capability sitting in a permanently-running build. It is the same "presence is the whole gate, add-and-remove-and-reflash is the lifecycle" shape as accept_foreign_pairing and recover_oneway_key, and the docs say so: remove the line once you are done enrolling.

What the enroll button sends (revised 2026-08-21, hardware-confirmed 2026-08-21). The documented 1W pairing handshake ("1W Discovery" in the published iown-homecontrol protocol notes) is 0x39 immediately followed by 0x30, both from the same controller, back to back within one gesture — and this project's own tests/corpus/captures/enrollment/somfy_smoove_enrollment_add_and_remove_controller_sx1276.yaml shows a real Somfy Smoove remote doing exactly that against a real Izymo, 128 ms apart, same burst. This ADR originally decided the enroll button would send 0x30 alone and keep 0x39 behind its own explicitly-named action, on the strength of a single 2026-08-13 bench success with 0x30 alone.

A 2026-08-21 retest against that same Izymo appeared to reproduce a failure with 0x30 alone, initially read as evidence of a stale controller-table slot needing 0x39 to clear. That reading was wrong. The retest's oneway_controllers config had been copied from an external bug report and carried io_device_type: roller_shutter, not light — 1W is class-addressed typed broadcast, so the frames never reached the Izymo at all, regardless of which handshake was used. Once the device class was corrected, both forms worked: 0x30 alone enrolled successfully, and so did 0x39 then 0x30. The stale-controller-table-slot hypothesis is therefore neither confirmed nor needed to explain anything observed so far — it remains a plausible failure mode for some other receiver family, just not a demonstrated one.

The enroll button sends 0x39 then 0x30 anyway — not because 0x30 alone is known to fail on this hardware, but because that is what a real remote's own pairing gesture does on the wire (the Smoove capture above), and matching the documented, hardware-observed handshake is the safer default for the many 1W receiver families this project has not bench-tested. 0x30-alone remains a known-working fallback if some other receiver ever turns out to react badly to the 0x39 prelude — nothing observed rules that out either, with two data points.

This does not weaken property 2 above. The 0x39 this button sends carries only this identity's own src address — nothing on the wire lets a 0x39 frame name a different controller for removal. So this prelude can only ever clear this identity's own prior entry before re-registering it; it still cannot touch another remote's registration. "Enrollment is additive across controllers, not a takeover" continues to hold; what changed is only that enrollment is no longer required to be non-destructive to a previous attempt by this same identity, which was never a safety property this ADR relied on.

Standalone removal stays behind its own action. oneway_remove_controller (the native API action that fires 0x39 alone, with no following 0x30) remains separate — for un-enrolling without immediately re-enrolling. What changed is only that "Enroll" no longer sends 0x30 in isolation; the self-directed 0x39 it now sends first was never the removal this section's original wording was guarding against.

This decision does not depend on standalone removal working. Safety here rests on enrollment being hard to trigger and low-consequence to other controllers when it happens, not on being able to undo it afterward.

Consequences

  • The risk is bounded to hardware the operator can physically reach, and further bounded by what a stray enrollment can actually do. A hub cannot enroll into a neighbour's actuator over the air — someone has to walk up to that actuator and hold its button first — and even if that happened unintentionally, the device's existing controller keeps working alongside the new one. Both limits are independent of each other and of this feature's own code.
  • No second entity, no confirmation state to reason about. The enroll button's only guard is the YAML build flag; whether a press does anything at all is decided entirely by the receiver.
  • Removal (oneway_remove_controller, 0x39) is not confirmed working on this project's test hardware. Repeated attempts had no observable effect. The leading hypothesis, by analogy with enrollment's own physical gate, is that 0x39 also needs the receiver in its association-mode window and the failed attempts were fired without it — but this is untested, not ruled out. Treat "enrollment is reversible" as design intent, not a demonstrated fact, until this is retested and confirmed.
  • Both enrollment failures traced to real users in the same week (2026-08-21: an external tester's Velux SML roller shutter report, and this project's own Izymo retest) turned out to share one root cause: a device-class mismatch in oneway_controllers' io_device_type, not the enrollment handshake. Once the class was corrected, the Izymo enrolled with either 0x30 alone or 0x39 then 0x30. Sending 0x39 first is not what fixed this class of failure and is not required to; it is kept because it matches a real remote's own captured on-wire behavior (tests/corpus/captures/enrollment/somfy_smoove_enrollment_add_and_remove_controller_sx1276.yaml). A different, still-live failure mode is a timing mismatch between the receiver's PROG hold and the controller's press — a long hold where a short press was needed, or vice versa — which the docs state both halves and their asymmetry explicitly for.
  • If a future revision ever discovers association mode can be triggered remotely, or held open indefinitely, on some device family, the first property above weakens and the arming-switch question should be revisited. Nothing observed so far suggests that; the additive-registration property would still hold regardless.